Network cable / Network device:CC-Link

Precautions

1. Please note that the transmission distance of the movable part cable is shorter than that of the fixing part cable.

[ High movable part cable (SCC110-HMV-7) ]

●When used alone: The transmission distance is 70% of the maximum transmission distance of the fixing part cable.
●When mixed use (when use the movable part cable and the fixing part cable together):Since the transmission distance corresponds to the distance of about 1.42 times the fixing part cable,please refer to the formula shown below.

Maximum transmission distance of CC-Link fixing part cable ≧
(CC-Link fixing part cable length) + (High movable part cable length × 1.42)


[ Movable part cable (FANC-110SBZ-5) ]

●When used alone: The transmission distance is 50% of the maximum transmission distance of the fixing part cable.
●When mixed use (when use the movable part cable and the fixing part cable together):Since the transmission distance corresponds to the distance of about 2 times the fixing part cable,please refer to the formula shown below.

Maximum transmission distance of CC-Link fixing part cable ≧
(CC-Link fixing part cable length) + (Movable part cable length × 2)


2. Cable compatible with Ver.1.10 can be mixed even with cables between different manufacturers.
3. When using an connector for connection, please check whether applicable wire specification of connector(conductor size, insulator external dimensions, etc.) conform to the cable.
4. When the equipment and cables of Ver.1.00 are mixed in the system,the cable length of station to station and the maximum total cable length are specified as Ver.1.00.
5. Ver.1.10 compatible cable can be used for Ver.2.00 equipment.
6. Please refer to the installation manual issued by the CC-Link Partner Association when laying CC-Link cable.
* About the specification of Ver.1.00 compatible cable, please inquire separately.