Specification
Dedicated flat cable ●CL9-FL4-18
Item |
Specification |
Cable type |
Flat cable |
Service temperature range |
-10 to 80℃ |
Rated voltage |
24 V DC |
Number of core wire |
4 |
Conductor size |
18 AWG |
Conductor material |
Tinned annealed copper wire bunch strand |
Conductor resistance (20℃) |
23.4 Ω/km or less |
Insulator material |
Non-lead heat resistant PVC |
Insulation resistance (20℃) |
10 MΩ or more |
Withstand voltage |
500 V AC for 1 minute |
▲ Page TOP
Exclusive movable cable ●CL9-MV4-075
Item |
Specification |
Cable type |
Round type cabtire cable for moving parts |
Service temperature range |
-10 to 105℃ |
Rated voltage |
24 V DC |
Number of core wire |
4 |
Conductor size |
0.75 mm2 |
Conductor material |
Annealed copper wire for electrical use |
Conductor resistance (20℃) |
26.0 Ω/Km |
Insulator material |
ETFE |
Insulation resistance (20℃) |
2500 MΩ · km or more |
Withstand voltage |
1500 V AC for 1 minute |
▲ Page TOP
Connector
Item |
Specification |
Service temperature range |
-20 to 85℃ (when 2 A is energized)
-20 to 70℃ (when 5 A is energized) |
Rated voltage |
24 V DC |
Rated current |
5.0 A |
Latch holding force |
98 N or more (vertical direction) |
Insertion durability |
300 insertions |
Insulation resistance |
1000 MΩ or more |
Withstand voltage |
1000 V AC for 1 minute |
Flame retardance |
UL 94 V-0 |
Applicable cable
Item |
Type |
VCTF cable |
Movable cable |
Number of core wire (color) |
4 cores (red, white, black, green) |
Conductor nominal cross-sectional area |
0.75 mm2 |
Cable insulator outer diameter |
φ2.1~2.4 |
φ1.8~2.1 |
Applicable cable |
Product conforming to JIS C 3306 |
CC-Link Association certified product(Model name:CL9-MV4-075) |
▲ Page TOP
Terminating resistor ●CL9-TERM
Item |
Specification |
Service temperature range |
-20 to 70℃ |
Rated voltage |
24 V DC |
Rated power |
1/2 W |
Latch holding force |
98 N or more (vertical direction) |
Insertion durability |
300 insertions |
Insulation resistance |
1000 MΩ or more |
Withstand voltage |
1000 V AC for 1 minute |
Flame retardance |
UL94 V-0 |
* Use terminating resistors of the same model name at both ends of the
trunk line.
▲ Page TOP
▲ Page TOP